Manual VIPA System 200V
Chapter 3 Deployment IM 253DP
HB97E - IM - RE_253-xDPxx - Rev. 12/44
3-23
IM 253-xDPx1 - DP-V1 slave - Parameters
At deployment of DP slaves presented in this manual there are parameters
for configuration that are individually used for every slave.
At usage of the corresponding GSD for DP-V0 operation you have the
following parameter data:
Byte
Bit 7 ... Bit 0
Default
0
Bit 1 ... 0: 0 (fix)
Bit 2: 0 = WD-Timebase 10ms
1 = WD-Timebase 1ms
Bit 4 ... 3: 0 (fix)
Bit 5: 0 = Publisher-Mode not available
1 = Publisher-Mode available
Bit 7 ... 6: 0 (fix)
00h
1 00h
(fix)
00h
2 08h
(fix)
08h
3 0Ah
(fix)
0Ah
4 81h
(fix)
81h
5 00h
(fix)
00h
6 00h
(fix)
00h
7
Bit 0: 0 = Enhanced diagnostic enable
1 = Enhanced diagnostic disable
Bit 1: 0 = Module status enable
1 = Module status disable
Bit 2: 0 = Channel-specific diagnostic enable
1 = Channel-specific diagnostic disable
Bit 3: 0 (fix)
Bit 4: 0 = V0: Manufacturer alarm not available
1 = V0: Manufacturer alarm available
Bit 5: 0 = V0: Diagnostic alarm not available
1 = V0: Diagnostic alarm available
Bit 6: 0 = V0: Process alarm not available
1 = V0: Process alarm available
Bit 7: 0 (fix)
70h
8
Bit 6 ... 0: 0 (fix)
Bit 7: 0 = Data format Motorola
1 = Data format Intel (only at analog modules)
00h
9 ... 12 00h (fix)
00h
Outline
Parameters
DP-V0
Summary of Contents for IM 253 DP Series
Page 1: ...VIPA System 200V IM Manual HB97E_IM RE_253 xDPxx Rev 12 44 November 2012...
Page 4: ...Contents Manual VIPA System 200V ii HB97E IM RE_253 xDPxx Rev 12 44...
Page 8: ...Safety information Manual VIPA System 200V 4 HB97E IM RE_253 xDPxx Rev 12 44...
Page 26: ...Chapter 1 Basics and Assembly Manual VIPA System 200V 1 18 HB97E IM RE_253 xDPxx Rev 12 44...
Page 100: ...Chapter 3 Deployment IM 253DP Manual VIPA System 200V 3 60 HB97E IM RE_253 xDPxx Rev 12 44...