Manual VIPA System 200V
Chapter 2 Hardware description
HB97E - IM - RE_253-xDPxx - Rev. 12/44
2-9
IM 253-2DP50 - DP-V0 slave (redundant) - Structure
•
2 redundant channels
•
DPR slave for max. 32 peripheral modules (max. 16 analog modules)
•
Max. 152Byte input data and 152Byte output data
•
Internal diagnostic protocol with a time stamp
•
Integrated DC 24V power supply for the peripheral modules (max. 3.5A )
•
Supports all PROFIBUS data transfer rates
[1]
LED Status DP2
[2]
RS485 interface DP2
[3] Address
selector
[4]
LED Status DP1
[5]
RS485 interface DP1
Front view
253-2DP50
PW
ER
RD
DE
IM 253 DPR
D
P
1
D
P
2
1
2
-
DC
24V
+
X1
VIPA 253-2DP50
X 2
3 4
PW
ER
RD
DE
9 9
1
2
3
4
5
6
[6]
Connector for DC 24V
power supply
1
2
+ DC 24 V
0 V
+
-
X1
DP1 / DP2
RS485
5
4
3
2
1
9
8
7
6
shield
n. c.
RxD/TxD-P (line B)
RTS
M5V
P5V
n. c.
RxD/TxD-N (line A)
n.c.
1
2
3
4
5
6
7
8
9
Via two 9pin RS485 sockets you include the 2 redundant channels into
PROFIBUS.
Properties
IM 253DPR
Interface
RS485 interface
Summary of Contents for IM 253 DP Series
Page 1: ...VIPA System 200V IM Manual HB97E_IM RE_253 xDPxx Rev 12 44 November 2012...
Page 4: ...Contents Manual VIPA System 200V ii HB97E IM RE_253 xDPxx Rev 12 44...
Page 8: ...Safety information Manual VIPA System 200V 4 HB97E IM RE_253 xDPxx Rev 12 44...
Page 26: ...Chapter 1 Basics and Assembly Manual VIPA System 200V 1 18 HB97E IM RE_253 xDPxx Rev 12 44...
Page 100: ...Chapter 3 Deployment IM 253DP Manual VIPA System 200V 3 60 HB97E IM RE_253 xDPxx Rev 12 44...