Manual VIPA System 200V
Chapter 3 Deployment IM 253DP
HB97E - IM - RE_253-xDPxx - Rev. 12/44
3-33
The interrupts section of the slave diagnostic provides information on the
type of interrupt and the cause that triggered the input. The interrupt section
has a maximum of 20bytes. A maximum of one interrupt can be used per
slave diagnostic. The interrupt component is always the last part of the
diagnostic frame.
The contents of the interrupt information depend on the type of interrupt:
•
In the case of
diagnostic interrupts
, the diagnostic data record 1 is send
as interrupt information (as of Byte x+4)
•
In the case of
process interrupts
, the additional information is 4bytes
long. These data is module specific and is described at the concerning
module.
If there is a diagnostic event for channel (/channel group) 0 of a module,
there may be a module error as well as a channel error. The entry is made
in this case even if you have not enabled the diagnostic for channel
(/channel group) 0 of a module.
The interrupt section is structured as follows:
Alarm status Byte x ... x+3
Byte
Bit 7 ... Bit 0
x
Bit 5 ... 0: 010100: Length of the interrupt section incl. Byte x
Bit 6 ... 7: Code for Module-Related diagnostic
x+1
Bit 0 ... 6: Type of interrupt
0000001:
Diagnostic
interrupt
0000010: Process interrupt
Bit 7: Code for interrupt
x+2
Bit 7 ... 0: Slot of the module that is producing interrupt 1 ... 32
x+3
Bit 1, 0:
00: Process interrupt
01:
Diagnostic
interrupt
incoming
10:
Diagnostic
interrupt
outgoing
11:
reserved
Bit 2: 0 (fix)
Bit 7 ... 3: Interrupt sequence number 1…32
Interrupts
Contents
Alarm status
Summary of Contents for IM 253 DP Series
Page 1: ...VIPA System 200V IM Manual HB97E_IM RE_253 xDPxx Rev 12 44 November 2012...
Page 4: ...Contents Manual VIPA System 200V ii HB97E IM RE_253 xDPxx Rev 12 44...
Page 8: ...Safety information Manual VIPA System 200V 4 HB97E IM RE_253 xDPxx Rev 12 44...
Page 26: ...Chapter 1 Basics and Assembly Manual VIPA System 200V 1 18 HB97E IM RE_253 xDPxx Rev 12 44...
Page 100: ...Chapter 3 Deployment IM 253DP Manual VIPA System 200V 3 60 HB97E IM RE_253 xDPxx Rev 12 44...