Checking the temperature limiter
If the burner control unit cannot be
reset after a fault shutdown, although
the boiler water temperature is below
approx. 90 °C:
&
Pull the leads off temperature limiter
A
.
&
Check the continuity of the tempera-
ture limiter with a multimeter.
&
Remove the faulty temperature lim-
iter.
&
Install a new temperature limiter.
&
After commissioning, press reset
button "
E
" on the control unit.
Repairs
(cont.)
80
Troubleshooting
5692
536
GB
Summary of Contents for Vitoplus 300
Page 103: ...Parts lists cont 103 Parts lists 5692 536 GB ...
Page 104: ...Parts lists cont 104 Parts lists 5692 536 GB ...
Page 105: ...Parts lists cont 105 Parts lists 5692 536 GB ...
Page 106: ...Parts lists cont 106 Parts lists 5692 536 GB ...
Page 107: ...Parts lists cont 107 Parts lists 5692 536 GB ...
Page 119: ...119 5692 536 GB ...