External operating mode changeover
The "External operating mode chan-
geover" function is connected via
external extension input
aVD
. Coding
address "91" enables the selection,
which heating circuits the operating
mode changeover should affect:
Coding
The op. mode changeover affects:
91:0
No changeover
91:1
Heating circuit without mixer A1
91:2
Heating circuit with mixer M2
91:3
Heating circuit without mixer and heating
circuit with mixer
With coding address "D5", you can
select in which direction the change-
over should be made for each heating
circuit:
Coding
The op. mode changeover affects:
d5:0
Changeover in the direction of "Constantly
reduced" or "Constantly standby" mode
(respectively in accordance with the se-
lected set value)
d5:1
Changeover towards "Constantly heating
mode"
The duration of the operating mode
changeover can be adjusted in coding
address "F2".
Coding
The op. mode changeover affects:
F2:0
No operating mode changeover
F2:1 to
F2:12
Duration of the operating mode change-
over 1 to 12 hours
The operating mode changeover
remains active for as long as the con-
tact remains closed, however at least
as long as the duration selected in
coding address "F2".
Control functions
91
Function description
5692
536
GB
Summary of Contents for Vitoplus 300
Page 103: ...Parts lists cont 103 Parts lists 5692 536 GB ...
Page 104: ...Parts lists cont 104 Parts lists 5692 536 GB ...
Page 105: ...Parts lists cont 105 Parts lists 5692 536 GB ...
Page 106: ...Parts lists cont 106 Parts lists 5692 536 GB ...
Page 107: ...Parts lists cont 107 Parts lists 5692 536 GB ...
Page 119: ...119 5692 536 GB ...