Coding in the delivered condition
Possible change
62:2
Circulation pump with
2 min run-on time
62:0
Circulation pump without
run-on
62:1
to
62:15
Run-on time adjustable
from 1 to 15 min
65:...
Information regarding
the type of diverter
valve (not adjustable)
65:0
Without diverter valve
65:1
Diverter valve by
Viessmann
65:2
Diverter valve by Wilo
65:3
Diverter valve by Grund-
fos
67:40
In conjunction with the
Vitosolic solar control
unit: Set DHW value 3
67:0
to
67:60
Set DHW value adjusta-
ble from 0 to 60 °C
6C:100
Set speed; internal cy-
linder primary pump
100%
6C:0
to
6C:100
Set speed adjustable
from 0 to 100%
6F:100
Maximum output for
DHW heating 100%, de-
faulted by the boiler
coding card
71:0
DHW circulation pump:
ON according to DHW
time program (separate
switching times are
possible for Vitotrol
300)
71:1
OFF during DHW heating
to set value 1
71:2
ON during DHW heating
to set value 1
72:0
DHW circulation pump:
ON according to DHW
time program
72:1
OFF during DHW heating
to set value 2
72:2
ON during DHW heating
to set value 2
73:0
DHW circulation pump:
ON according to DHW
time program
73:1
to
73:6
During the time program
1x/h ON for 5 min
up to 6x/h ON for 5 min
73:7
Constantly ON
General
76:0
Without LON communi-
cation module
76:1
With LON communication
module; automatic recog-
nition
Code 2
(cont.)
48
Coding
5692
536
GB
Summary of Contents for Vitoplus 300
Page 103: ...Parts lists cont 103 Parts lists 5692 536 GB ...
Page 104: ...Parts lists cont 104 Parts lists 5692 536 GB ...
Page 105: ...Parts lists cont 105 Parts lists 5692 536 GB ...
Page 106: ...Parts lists cont 106 Parts lists 5692 536 GB ...
Page 107: ...Parts lists cont 107 Parts lists 5692 536 GB ...
Page 119: ...119 5692 536 GB ...