Display fault
code
System char-
acteristics
Cause
Measures
9F
Control mode
Solar control unit fault
message
See solar control
unit service in-
structions
A7
Control mode
as per the de-
livered condi-
tion
Faulty programming unit
Replace program-
ming unit
b0
Burner
blocked
Flue gas temperature
sensor shorted out
Check the flue
gas temperature
sensor (see
page 79)
b8
Flue gas temperature
sensor break
b1
Control mode
as per the de-
livered condi-
tion
Communication error pro-
gramming unit (internal)
Check connec-
tions and replace
programming unit,
if required
b4
Regulates as if
the outside
temperature
was 0 °C
Internal fault analog con-
verter
Replace the con-
trol unit
b5
Control mode
as per the de-
livered condi-
tion
Internal fault
Replace the con-
trol unit
b7
Burner
blocked
Boiler coding card miss-
ing, faulty or incorrect
boiler coding card
Plug in boiler cod-
ing card or re-
place, if faulty
bA
Mixer M2 regu-
lates in accor-
dance with the
last trans-
mitted set
value
Communication fault
–
extension kit for heating
circuit with mixer M2
Check the exten-
sion kit connec-
tions and coding.
Start the exten-
sion kit.
bC
Control mode
without remote
control
Communication fault
–
Vitotrol remote control,
heating circuit A1
Check connec-
tions, cable, cod-
ing address "A0"
and the remote
control DIP
switches
Fault codes
(cont.)
70
Troubleshooting
5692
536
GB
Summary of Contents for Vitoplus 300
Page 103: ...Parts lists cont 103 Parts lists 5692 536 GB ...
Page 104: ...Parts lists cont 104 Parts lists 5692 536 GB ...
Page 105: ...Parts lists cont 105 Parts lists 5692 536 GB ...
Page 106: ...Parts lists cont 106 Parts lists 5692 536 GB ...
Page 107: ...Parts lists cont 107 Parts lists 5692 536 GB ...
Page 119: ...119 5692 536 GB ...