Coding
Internal
circulation
pump
Heating cir-
cuit pump
Heating cir-
cuit without
mixer
Heating cir-
cuit pump
Heating cir-
cuit with
mixer
Cylinder primary pump
21
ON
OFF
Control funct.
OFF
22
ON
OFF
OFF
Control funct.
23
ON
OFF
OFF
OFF
Coding in the delivered condition
Possible change
Boiler/burner
52:0
Without flow tempera-
ture sensor for low loss
header
52:1
With flow temperature
sensor for low loss head-
er (automatic adjustment
after recognition)
54:0
Without solar control
unit
54:1
With the Vitosolic 100
54:2
With the Vitosolic 200
(automatic adjustment on
recognition)
Domestic hot water
56:0
DHW temperature ad-
justable from 10 to
60 °C
56:1
DHW temperature adjus-
table from 10 to above
60 °C (max. value subject
to boiler coding card)
Observe the max. per-
missible DHW tempera-
ture
58:0
Without auxiliary func-
tion for DHW heating
58:10
to
58:60
Input of a second set
DHW value; adjustable
from 10 to 60 °C
59:0
Cylinder heating:
Starting point -2.5 K
Stopping point +2.5 K
59:1
to
59:10
Starting point adjustable
from 1-10 K below the set
value
5b:0
DHW cylinder directly
connected to the boiler
5b:1
DHW cylinder connected
downstream of the low
loss header
60:20
During DHW heating,
the boiler water tem-
perature is a maximum
of 20 K higher than set
DHW temperature
60:5
to
60:25
The difference between
the boiler water tempera-
ture and the set DHW
temperature is adjustable
from 5 to 25 K
Code 2
(cont.)
47
Coding
5692
536
GB
Summary of Contents for Vitoplus 300
Page 103: ...Parts lists cont 103 Parts lists 5692 536 GB ...
Page 104: ...Parts lists cont 104 Parts lists 5692 536 GB ...
Page 105: ...Parts lists cont 105 Parts lists 5692 536 GB ...
Page 106: ...Parts lists cont 106 Parts lists 5692 536 GB ...
Page 107: ...Parts lists cont 107 Parts lists 5692 536 GB ...
Page 119: ...119 5692 536 GB ...