Coding in the delivered condition
Possible change
77 :1
LON user number
77 :2
to
77 :99
LON user number, adjus-
table from 1 to 99:
1-4 = boiler
5 = cascade
10 - ... = Vitotronic 050
99 = Vitocom
Note
Allocate each number
only
once.
79:1
Control unit is fault
manager
79:0
Control unit is not fault
manager
7b:1
Send time via LON
7b:0
Do not send time via LON
7F:1
Detached house
7F:0
Apartment block
Separate adjustment for
holiday program and time
program for DHW heat-
ing, as option
80:1
With a 5 second time
delay for fault message;
message will be issued,
if a fault persists for at
least 5 seconds
80:0
Without time delay
80:2
to
80:199
Time delay adjustable
from 10 to 995; 1 step =
5 s
81:1
Automatic summer/win-
ter time changeover
81:0
Manual summer/winter
time changeover
81:2
The radio clock module
will be recognised auto-
matically
81:3
Accept time via LON
88 :0
Temperature displayed
in Celsius
88 :1
Temperature display in
Fahrenheit
90:128
Time constant for calcu-
lating adjusted outside
temperature 21.3 h
90:0
to
90:199
Fast (low values) or slow
(high values) matching of
the flow temperature,
subject to the set value
when the outside tem-
perature changes;
1 step = 10 min.
Code 2
(cont.)
49
Coding
5692
536
GB
Summary of Contents for Vitoplus 300
Page 103: ...Parts lists cont 103 Parts lists 5692 536 GB ...
Page 104: ...Parts lists cont 104 Parts lists 5692 536 GB ...
Page 105: ...Parts lists cont 105 Parts lists 5692 536 GB ...
Page 106: ...Parts lists cont 106 Parts lists 5692 536 GB ...
Page 107: ...Parts lists cont 107 Parts lists 5692 536 GB ...
Page 119: ...119 5692 536 GB ...