13
Section number
5
7
L [mm]
680
872
Fig. no. 8
Bedding dimensions
The boiler placing with respect to the necessary handling space:
•
basic surroundings of AA5/AB5 according to
Č
SN 33 2000-1 ed. 2;
•
handling space of minimum 1000 mm in front of the boiler must be maintained;
•
a minimum distance of 400 mm between the back part of the boiler and the wall;
•
from the side of the boiler there must be maintained a space at least 500 mm for the door opening and
for the access to the rear part of the boiler;
•
a minimum distance of 100 mm from the side wall.
•
a minimum boiler-room height 2 100 mm
Fig. no. 9
Boiler placing in a boiler room
Fuel placing:
•
dry fuel (up to the 12% moisture) must be used in order to guarantee the correct combustion in the
boiler. The pellets should be stored in their original packing from the manufacturer
(e.g. PET sacpcs) at a dry place;
•
it is impossible to store fuel behind the boiler or unload it next to the boiler in a distance smaller than
400 mm;
•
the manufacturer recommends that min. 1000 distance is kept between the boiler and fuel or the fuel is
placed in a room different from that where the boiler is installed