38
Tab. no. 7 Description of operating parameters of control module of burner 32S
number of flickers of
yellow LED
Index of potentiometer
P1
P2
P3
P4
P5
Operating time (s)
Index
0
30
1,50
30
45
0
1
45
1,65
60
90
1
2
60*
1,82
90
135
2
3
75
2,18
120
180
3
4
90
2,83
150*
225
4
5
105
3,68
180
270
5
6
120
4,79
210
315
6
7
135
6,22
240
360
7*
8
150
7,46
270
405
8
9
165
8,21
300
450*
9
*
factory setting
Tab. no. 8
Setting of burner output by means of potentiometer
Heat output of boiler [kW]
P2
(number of flickers of yellow LED)
VIADRUS HERCULES Green Eco Therm
25S
32S
0
5,0
5,0
1
6,0
6,0
2
8,0
8,0
3
11,0
11,0
4
14,0
14,0
5
18,0
18,0
6
21,0
21,0
7
25,0
25,0
8
-
28,0
9
-
32,0
WARNING:
In case a dark yellow flame and black smoke escape from the chimney, we should reduce burner output by
means of potentiometer or the valve of fan should be opened.
When using the recommended fuel, the parameters that are listed in Tab. no. 8 correspond to a good quality
of combustion and operation of burner.
•
Setting of burner output could be achieved by determining the amount of supplied fuel at nominal
operating mode - the amount of fuel transported by auger during a certain time interval in nominal
operating mode. Here it is necessary to take into account the fuel heat efficiency and boiler efficiency.
•
To determine the amount of dosed fuel proceed as follows:
•
Disconnect the transport hose from the knee of the burner.
•
Insert the end of the hose into a prepared vessel.
•
Turn on the main switch of boiler to ON position and select the operating temperature of the operating
thermostat.
•
Disconnect the photosensor by pulling it out of the fixture (this is evaluated on the control panel as the
ignition and operation at rated power)
•
Dosing of fuel for rated output will run in this mode
For example:
The measured time interval is 15 minutes (which is 1/4 hours) and the amount of fuel accumulated in the
vessel is 1,325 kg. Calculation shows that the amount of supplied fuel is 5.3 kg / h;