Environmental conditions
▪
Ambient Temperature: 0º to 49º C or 32º to 120º F
▪
The room must be dust free and clean.
▪
It is optimal to mount the enclosure on fire rated plywood which is affixed to a cinder block wall or a wall
covering i.e. sheetrock
▪
Mount the cabinet in a secure, but generally accessible location
Mounting the enclosure
▪
Field Wiring
– It is recommended that you drill holes or punch the knockouts in the metal enclosure for field
wiring before mounting the enclosure to the wall.
▪
A non-metallic sleeve is recommended to protect the wiring where it enters the cabinet.
▪
Mount the enclosure to the wall using the provided mounting holes. Recommended mounting hardware:
Four 1
/4” x 1” lag bolts.
PIN Layout
Configuration
The VRI-1S3 will be connected to the
bright blue
via RS-485 protocol. A maximum of 16 reader interfaces can
be connected to one
bright blue
data channel. Wire runs are limited to 4,000 feet (Data Only) from the
bright
blue
to a VRI-1S3 (
see Recommended Wire Chart
). Data communication between
bright blue
and the reader
interfaces can be a multiplex or a daisy chain configuration.
Multiplex configuration