                         ADDRESSABLE RATE OF RISE HEAT DETECTOR

103 (diam.) x 48 (height)

 mm

Alarm LED 

A2R

IP20

EN 54-5

o

-10 to 55  C

Up to 95% 

2 years

145gr.

TECHNICAL CHARACTERISTICS

 BSR-6060/A

IDLE STATE POWER CONSUMPTION
ALARM POWER CONSUMPTION

PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE

DEGREES OF COVER PROTECTION

OPERATION VOLTAGE

RELATIVE HUMIDITY

TYPICAL WEIGHT 

EXTERNAL DIMENSIONS 

GUARANTEE

INDICATORS

CLASS

Page 1 from 3

21-28V DC

1.5 mA (with indication LED activated)

1mA

GENERAL

Before installing the detector, the user must 
read  these  instructions  carefully  and  store 
this manual for future  reference.BSR-6060/A 
is  a  thermal  and  rate  of  rise  detector 
simultaneously. It co-operates with BSR-1116 
and BSR-2100 panels.
The  device  transmits  an  analogue  value  to 
the  panel  which  depends  of  the  area’s 
temperature and the rate of temperature rise. 
The  analogue  value  is  100  (temperature 

o

56 C) and increases one unit per degree of   
the temperature  increase. If the temperature 

o

rises  rapidly  (over  5 C  per  minute)  then  the 
analogue value that sends the detector to the 
panel is 127. Analogue value setting 100 is 
approved to EN 54-5: 2000 + A1: 2002.
The detector have two parts, one plastic base 
which is installed on the ceiling and the main 
unit of the detector which is fastened to the 
base by a simple turning to the right.                
The detectors have an   indication   led which 
lights  continuously  in  case  of  fire  detection 
until  there  is  a  reset  signal  from  the  panel.   
When we silence the sirens the LED remains 
lit  to  show  us  the  detector  that  issued  the 
alarm. The LED goes off when we RESET the 
panel. The indication led also flashes every 8 
sec to indicate good operation.

To set each detector’s address you have to 
use the device BSR-2143 photo. 1. (refer to 
it’s  instruction  manual).  After  the  address 
setting  mark this number to the sticker on the 

ADDRESS SETTING

detector’s  base  (ADR:XXX).  Each  detector 
must have an 
address  with  which  it  is  recognized  from  the 
panel.
It`s  forbidden  for  two  devices  with  same 
addresses to be connect  to  the  same  loop. 
 

OPERATION CHECK 

It is advised to conduct a good operation test 
every  6  months  and  every  time  the  detector   
position is changed. 
It  is  essential  to  have  good  air  circulation 
inside   the detector. Therefore care must be 
taken so  that the vents of the detector are not 
covered. 

NOTE

The detectors must be placed in the ceiling on 
visible areas with no side obstacles and away 
from sides with no air circulation or strong air 
currents  and  vapors.  Each  detector  covers 

2     

almost 50 m

and the distance between two 

detectors must not exceed 15m. 
The cables cross section must be from 0.5 to 

2

1.5mm . 

ATTENTION!!

After  the  device  is    installed,  care  must  be   
taken,  so  that  the  detector  vents  are  not 
blocked by   anything (i.e. dust, paint). Failing 
to  do    so  will  prevent  the  air  to  enter    the   
detector.

After  the  installation,  it  is  the  sole 
responsibility  of  the  user  to  maintain 
the detector  for  good  operation

921606002_09_014

Thank you for your trust in our products.  

Olympia Electronics -  European manufacturer.