VBBIM09/33/20 v5.0.3
Chapter 15 Schlage Wireless Readers
215
4
After this connection is made, hold down one of the PIM link switches (SA or SB).
a) Continue to hold the link switch and press the reset button (S3). Do not stop pressing the link switch.
b) The
LED’s (CR6 – 10) on the PIM begin flashing, displaying the firmware version of the PIM. When
completed, (CR7 and 10) will continue to flash RED and CR15 will be continue to blink GREEN. At this
point, the PIM will be in the CDT link mode as long as the CDT program on the PC remains running and
connected to the PIM.
c) Release the link switch.
d) On the CDT screen, under PIM Status you should now see the "PIM Connected on Proper Com Port"
message.
5
Using the Addresses tab, set the address of the PIM.
a) If one PIM is being used per channel set the
PIM Addr
to 0.
b) If more than one PIM is being used per channel set the PIM Addr of each PIM to the lowest number in
the address range. (See the next step for details on address range.)
Example: Channel 1 of
bright blue
will have two PIMs. One PIM will be interfacing with 5 WAPMs and
the other will be interfacing with 6. The first PIM will have an Addr Lo of 0 and an Addr Hi of 4. The PIM
Addr for this PIM will be 0. The second PIM, when configured, will have an Addr Lo of 5 and an Addr Hi
of 10. The PIM Addr for this PIM will be 5.
Note:
The PIM Addr setting should always be equal to the Addr Lo setting.
Example address settings for a single PIM on a channel
6
Using the Addresses tab, set the range of address for the WAPMs interfacing with the PIM.
a) If one PIM is being used per channel set the
Addr Lo
to 0 and the
Addr Hi
to 15.