vacon • 37
Description of Groups
3
3.4
System parameters, Faults and History faults: Menu FLT
Code
Parameter
Min
Max
Unit
Defa
ult
ID
Description
V1.1
API system SW ID
2314
V1.2
API system SW version
835
V1.3
Power SW ID
2315
V1.4
Power SW version
834
V1.5
Application ID
837
V1.6
Application Ver.
838
V1.7
System load
839
When no fieldbus board has been installed, the following values are visible:
V2.1
Communication status
808
Status of Modbus
communication.
Format: xx.yyy
where xx = 0 - 64
(Number of error
messages) yyy = 0 -
999 (Number of good
messages)
V2.9
Last communication fault
816
The fault code related to the
last counted bad messages is
shown:
1 = Illegal function
2 = Illegal address
3 = Illegal data value
4 = Illegal slave device
53 = USART receive fault
(parity error/ frame error/
USART buffer overflow)
90 = Receive buffer overflow
100 = Frame CRC Error
101 = Ring buffer overflow
P2.2
FB Protocol Status
0
1
0
809
0 = Not used
1 = Modbus used
P2.3
Slave address
1
255
1
810
P2.4
Baud rate
0
8
5
811
0 = 300
1 = 600
2 = 1200
3 = 2400
4 = 4800
5 = 9600
6 = 19200
7 = 38400
8 = 57800
P2.6
Parity type
0
2
0
813
Parity type:
0 = None
1 = Even
2 = Odd
Stop bit:
- 2-bits with parity type
“None”;
- 1-bit with parity type “Even”
and “Odd”.
Table 21. System parameters, Faults and History faults.