Description of Groups
vacon • 32
Service support: find your nearest Vacon service center at www.vacon.com
3
3.3.11
Group Fieldbus: Menu PAR G11
Code
Parameter
Min
Max
Unit
Default
ID
Description
P11.1
FB DataOut 1 Sel
0
17
0
852
Variable mapped on PD1:
0 = Output frequency
1 = Motor speed
2 = Motor current
3 = Motor voltage
4 = Motor torque
5 = Motor power
6 = DC-link voltage
7 = Active fault code
8 = Analogue AI1
9 = Analogue AI2
10 = Digital inputs state
11 = PID feedback value
12 = PID setpoint
13 = Power kW
14 = Energy
15 = Flow
16 = Volume 1
17 = Volume 2
P11.2
FB DataOut 2 Sel
0
17
1
853
Variable mapped on PD2. See
P11.1
P11.3
FB DataOut 3 Sel
0
17
2
854
Variable mapped on PD3. See
P11.1
P11.4
FB DataOut 4 Sel
0
17
3
855
Variable mapped on PD4. See
P11.1
P11.5
FB DataOut 5 Sel
0
17
4
856
Variable mapped on PD5. See
P11.1
P11.6
FB DataOut 6 Sel
0
17
5
857
Variable mapped on PD6. See
P11.1
P11.7
FB DataOut 7 Sel
0
17
6
858
Variable mapped on PD7. See
P11.1
P11.8
FB DataOut 8 Sel
0
17
7
859
Variable mapped on PD8. See
P11.1
P11.9
FB Aux CW selection
0
5
0
1821
PDI for Aux CW
0 = Not used
1 = PDI1
2 = PDI2
3 = PDI3
4 = PDI4
5 = PDI5
P11.10
FB PID setpoint
selection
0
5
1
1822
PDI for PID Setpoint
See P11.9
P11.11
FB PID actual
selection
0
5
2
1823
PDI for PID Feedback
See P11.9
P11.12
FB AnalogueOut cntrl
selection
0
5
3
1824
PDI for Analogue Out CTRL
See P11.9
Table 17. Fieldbus group.
NOTE!
Visibility of the group depends on P1.16.