Description of Groups
vacon • 20
Service support: find your nearest Vacon service center at www.vacon.com
3
3.3.2
Group Advanced Settings: Menu PAR G2
Code
Parameter
Min
Max
Unit
Default
ID
Description
P2.1
Start/Stop logic
0
4
0
300
Logic = 0:
Start sign 1 = Start Forward
Start sign 2 = Start Back-
ward
Logic =1:
Start sign 1 = Start
Start sign 2 = Reverse
Logic = 2:
Double Start
Logic = 3:
Start sign 1 + Analogue sign
Logic = 4:
Solar only
P2.2
Preset speed 1
0.00
P1.2
Hz
10.00
105
Multistep speed 1
P2.3
Preset speed 2
0.00
P1.2
Hz
15.00
106
Multistep speed 2
P2.4
Preset speed 3
0.00
P1.2
Hz
20.00
126
Multistep speed 3
P2.9
Start acceleration time
0.1
3000.0
s
1.0
502
Time from 0 to min fre-
quency
P2.14
Control place 2
0
2
0
1806
Alternative control place:
0: I/O terminals
1: Keypad
2: Fieldbus
P2.15
Frequency reference
source 2
0
7
1
1820
Selection of reference
source:
0 = AI1
1 = AI2
2 = PID reference
3 = not used
4 = Keypad
5 = Fieldbus
6 = AI1+AI2
7 = Max Frequency
P2.22
Stop button active
0
1
1
114
0 = Limited function of Stop
button
1 = Stop button always
enabled
P2.23
Keypad Reverse
0
1
0
123
Direction of motor rotation
when control place is key-
pad
0 = Forward
1 = Reverse
Table 7. Advanced settings group.
NOTE!
Visibility of the group depends on P1.16.
P2.18 - P2.21 are available only with Mains connected.
Summary of Contents for 20 CP/X
Page 1: ...vacon 20 cp x ac drives Solar pump application manual ...
Page 2: ......
Page 4: ...vacon 1 5 Fault tracing 82 ...
Page 6: ...1 vacon 3 Safety ...
Page 16: ...vacon 13 Solar pump Application 2 ...
Page 90: ......
Page 91: ......