Description of Groups
vacon • 24
Service support: find your nearest Vacon service center at www.vacon.com
3
3.3.5
Group Digital outputs: Menu PAR G5
Code
Parameter
Min
Max
Unit
Default
ID
Description
P5.1
Relay output 1 content
0
13
1
313
Function selection for RO1:
0 = Not used
1 = Ready
2 = Run
3 = General fault
4 = General fault inverted
5 = Warning
6 = Reversed
7 = At speed
8 = Output freq. supervision
9 = Output current superv.
10 = Analogue input superv.
11 = Fieldbus 1
12 = Fieldbus 2
13 = Fault/Warning
P5.2
Relay output 2 content
0
13
2
314
See P5.1
P5.3
Digital output content
0
13
3
312
See P5.1
P5.4
Relay output 1 on delay
0.00
320.00
s
0.00
458
ON delay for relay
P5.5
Relay output 1 off delay
0.00
320.00
s
0.00
459
OFF delay for relay
P5.6
Relay output 1 inversion
0
1
0
1804
0 = no inversion
1 = inverted
P5.7
Relay output 2 on delay
0.00
320.00
s
0.00
460
See P5.4
P5.8
Relay output 2 off delay
0.00
320.00
s
0.00
461
See P5.5
P5.9
Exp. EO1 output content
0
13
0
1826
Parameter visible when a I/
O expansion board is
installed. See P5.1 for
selection
P5.10
Exp. EO2 output content
0
13
0
1827 See P5.9
P5.11
Exp. EO3 output content
0
13
0
1828 See P5.9
P5.12
Exp. EO4 output content
0
13
0
1872 See P5.9
Table 11. Digital outputs group.
NOTE!
Visibility of the group depends on P1.16.
P5.9 is visible when OPTB2,OPTB5, OPTB9 or OPTBF is installed (first relay EO1).
P5.10 is visible when OPTB2 or OPTB5 is installed (second relay EO2).
P5.11 is visible when OPTB5 is installed (third relay EO3).
P5.12 is visible when OPTBF is installed (digital output EO4).