vacon • 63
Parameter description
4
4.9
Protections
P9.1 R
ESPONSE
TO
4
M
A
REFERENCE
FAULT
(AI< 4mA)
0: No action
1: Warning
2: Fault
3: Warning if Start active
4: Fault if Start active
Analogue reference below 4mA.
P9.2 4
M
A
FAULT
DETECTION
TIME
Delay as filter on fault generation
P9.3 E
ARTH
FAULT
PROTECTION
0: No action
1: Warning
2: Fault
Output currents sum not zero.
P9.4 M
OTOR
S
TALL
PROTECTION
0: No action
1: Warning
2: Fault
This is an overload protection. Stall is recognized by maximum motor current (=P1.5) and low
output frequency.
Figure 13. Stall characteristic settings.
f
I
Par. P1.5
Par. P9.6
Stall area