vacon • 61
Parameter description
4
Figure 12. Programmable curve.
P8.5 U/
F
CURVE
MIDPOINT
FREQUENCY
Enabled if P8.4= 2.
Note
: motor identification automatically sets this parameter.
P8.6 U/
F
CURVE
MIDPOINT
VOLTAGE
Enabled if P8.4= 2.
Note
: motor identification automatically sets this parameter.
P8.7 O
UTPUT
VOLTAGE
AT
ZERO
FREQUENCY
Motor voltage at frequency zero.
Note
: motor identification automatically sets this parameter.
P8.8 S
WITCHING
FREQUENCY
PWM frequency. Values above default can cause thermal overload of the drive. Motor noise can
be minimized using a high switching frequency. Increasing the switching frequency reduces
the capacity of the drive. It is recommended to use a lower frequency when the motor cable is
long in order to minimize capacitive currents in the cable.
P8.11 DC
BRAKING
CURRENT
DC current injected at start or stop.
U[V]
f[Hz]
P2
P3
P1
Default: Nominal
voltage of the motor
Linear
Field
weakening
point
Default:
Nominal frequency
of the motor