Parameter description
vacon • 52
Service support: find your nearest Vacon service center at www.vacon.com
4
P3.9 S
TART
SIGNAL
SELECT
Run command is set when Start 1 signal is high and a selectable analogue input is below (or
above) a programmable threshold.
This can be used for a tank level control, where the analogue measurement is used for both
starting the pump and controlling the speed.
P3.10 S
TART
LEVEL
Unscaled analogue signal
If P3.10 < P3.11:
Start below this level
If P3.10> P3.11:
Start above this level
P3.11 S
TOP
LEVEL
Unscaled analogue signal
If P3.11> P3.10:
Stop above this level
If P3.11 < P3.10:
Stop below this level