vacon • 21
Description of Groups
3
3.3.3
Group Analogue inputs: Menu PAR G3
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.1
AI1 signal range
0
1
0
379
0 = 0…10V / 0…20mA
1 = 2…10V / 4…20mA
P3.2
AI1 custom min
-100.00
100.00
%
0.00
380
Custom range min setting
20% = 4-20 mA/2-10 V
P3.3
AI1 custom max
-100.00
300.00
%
100.00
381
Custom range max setting
P3.4
AI1 filter time
0.0
10.0
s
0.1
378
Filter time for analogue
input 1
P3.5
AI2 signal range
0
1
1
390
0 = 0…10V / 0…20mA
1 = 2…10V / 4…20mA
P3.6
AI2 custom min
-100.00
100.00
%
0.00
391
See P3.2
P3.7
AI2 custom max
-100.00
300.00
%
100.00
392
See P3.3
P3.8
AI2 filter time
0.0
10.0
s
0.1
389
See P3.4
P3.9
Star signal select
0
1
0
1810
0 = AI1
1 = AI2
P3.10
Start level
0.00
100.00
%
10.00
1857
Not scaled analogue signal
If P3.10 < P3.11:
Start below this level
If P3.10> P3.11:
Start above this level
P3.11
Stop Level
0.00
100.00
%
60.00
1856
Not scaled analogue signal
If P3.11> P3.10:
Stop above this level
If P3.11 < P3.10:
Stop below this level
Table 9. Analogue inputs group.
NOTE!
Visibility of the group depends on P1.16.