vacon • 23
Description of Groups
3
P4.22
Minimum level logic
0
1
0
1965
Selections for minimum
water level logic:
0 = water level is ok when
digital input for Minimum
water level is high
1 = water level is ok when
digital input for Minimum
water level is low
The drive trips with F63 (Low
water level) when water level
is not ok. The fault is reset
with autoreset logic of
Underload (see P10.4 - 7)
when level is restored.
Min level signal/fault refers
to level in a well from which
water is taken.
P4.23
Maximum water level
0
6*
0
1966 Digital input for water level
P4.24
Maximum level logic
0
1
0
1967
Selections for maximum
water level logic:
0 = water level is ok when
digital input for Maximum
water level is high
1 = water level is ok when
digital input for Maximum
water level is low
The drive trips with F64 (Max
water level) when water level
is not ok. The fault is reset
with autoreset logic of
Underload (see P10.4 - 7)
when level is restored.
Max level signal/fault refers
to level in a possible tank
where pumped water is
stored.
NOTE!
(*)The maximum value is higher when an optional board with digital inputs is
installed. Parameter is automatically reset if value is greater than present limit.
NOTE!
Visibility of the group depends on P1.16.
Table 10. Digital inputs group.