vacon • 71
Parameter description
4
P11.12 FB
A
NALOGUE
O
UT
CNTRL
SELECTION
Parameter defines the input process data coupled to analogue output control. Selections as
P11.9.
4.11.1
Fieldbus mapping
4.11.1.1
Fieldbus Data IN: Master -> Slave
Notes:
•
CW b0 Run is acquired on edge, only if the drive is in Ready state (see Status Word b0)
and actual control place is Fieldbus.
•
CW b2 Fault Reset is active even if control place is not the Fieldbus.
•
Fieldbus different from Modbus have their own Control Word (see manual of the specific
fieldbus board).
Modbus
register
Name
Description
Range
2001
Control word(*)
Drive control
Binary coded:
b0: Run
b1: Reverse
b2: Fault Reset (on edge)
b8: forces control place to
fieldbus
b9: forces reference source
to fieldbus
2002
General control word
Not used
2003
Speed reference(*)
Reference
0...10000 as 0,00...100,00%
of Min freq. - Max freq.
range
2004
Fieldbus Data IN 1
Programmable
0...10000
2005
Fieldbus Data IN 2
Programmable
0...10000
2006
Fieldbus Data IN 3
Programmable
0...10000
2007
Fieldbus Data IN 4
Programmable
0...10000
2008
Fieldbus Data IN 5
Programmable
0...10000
2009
Fieldbus Data IN 6
Not used
-
2010
Fieldbus Data IN 7
Not used
-
2011
Fieldbus Data IN 8
Not used
-
Table 26. (*) Modbus Data inputs. They can vary depending on fieldbus used (See
specific fieldbus option board installation manual).