vacon • 79
Parameter description
4
4.13.2.4
P&O in local max points
A panel with partial irradiation, or somehow defective, could cause a discontinuity on the pow-
er/voltage curve of the array. In this situation the basic P&O logic (perturb and observe) could
lead to a local maximum point, that is not corresponding to maximum available power.
Figure 19.
P14.15 P&O
LOCAL
MAX
STEP
To bypass discontinuity on power/voltage curve of array, after having reached a stable point,
the P&O takes a bigger downward step (P14.15) in voltage. This step allows to overcome the
local maximum and continue to search for the actual MPP.
If the point is the real MPP, the lower voltage reference will cause a drop in DC voltage and
some oscillations, that are recognized and automatically damped by increasing the DC voltage
reference.
The function can be disabled by programming P14.15= 0V.
P14.16
P&O
LOCAL
MAX
TIME
Further attempts to reach a higher MPP after an unsuccessful attempt will follow only after
the programmable masking time (P14.16).
P14.17
P&O
LOCAL
MAX
FREQ
The downward step is done only when output frequency is above minimum fre P14.17.
Voltage across PV array (V)
P
o
w
e
r f
rom PV ar
ray (W
)
50
100
150
200
2
1.5
1
0.5
0
2.5
250
3
0
x10
4
P
MAX1
P
MAX2
P
MAX3
Local maximum points
Global maximum point