47
System Start-up Instructions
1. Once all the plumbing has been connected, slowly open the main water shutoff valve.
Make sure the inlet and outlet valves on the injection panel are open. Open a spigot
downstream of the entire system to release the air. Run the water through the system
plumbing. The injection panel will be operating during this period and the Fusion Carbon
Superfilter and GreenWave tanks will be in the bypass position.
2. Once the air is out of the plumbing, close the downstream spigot and let the plumbing
system pressurize. Check all the plumbing connections for leaks. If there are leaks fix
them immediately. Especially around the electronic components.
3. Now push the red button on the top of the 5 micron and 1 micron filter housings and bleed
the air until water is coming out of the red button.
4. Plug the Superfilter valve into an approved power source that is constantly energized.
5. When power is supplied to the control valve, the screen will display “INITIALIZING WAIT
PLEASE” while it finds the service position.
6. Once the valve has settled on the time of day, start an Immediate Manual Regeneration
(See page 36). The valve will immediately start moving to the BACKWASH position.
7. Open the inlet on the bypass valve slowly and allow water to enter the unit. Allow all air to
escape from the unit before turning the water on completely. Air will be pushed out of the
drain line when the Superfilter is in the backwash cycle. Be sure to secure the drain line
because the air and water will be moving through the drain line with force. Allow the wa-
ter to run to drain for the entire backwash cycle or until all carbon media fines are washed
out of the filter indicated by clear water coming from the drain hose. The peroxide should
be injecting during this procedure.
8. When the backwash cycle is complete the valve will advance to the RINSE position.
Check the drain line flow. Allow the water to run for the entire RINSE cycle until the water
is clear. You may see some bubbles in the water but there should be no bursts of air
coming out of the Superfilter.
9. The valve will automatically advance to the SERVICE position after the RINSE cycle is
complete. Open the outlet valve on the control valve bypass, then open the nearest treat-
ed water faucet and allow the water to run until clear, close the tap and replace the faucet
screen.
10. Program time, date, and number of days between regenerations into controller using
Programming Instructions.
Installation, Operation and Maintenance Manual
385-GWU-1000, 385-GWU-1500, 385-GWU-2000