29
1. Plug the chemical injection panel in the wall. Pour the supplied Hydrogen Peroxide
into the chemical solution tank. Unplug the pump power cord from the PCM on the
injection panel and attach it to an extension cord that is energized. Turn the switch
on the injection pump to the “on” position and allow the chemical pump to prime with
peroxide. Typically the peroxide can be seen traveling through the tubing. Once the
pump is primed (solution is pumped from the tank through the pump and to injection
port, unplug the pump from the extension cord and plug it back into the PCM on the
injection panel. Set the adjustment knob on the PCM to 50%
Chemical Injection Panel Start-up Instructions
PCM
Injection Pump
Plug
Pump Rate
Control Knob
Installation, Operation and Maintenance Manual
385-GWU-1000, 385-GWU-1500, 385-GWU-2000