5.COMPARISON SETTING
25
■
HI/LO limit comparison selection
Valid when “HI
-
LO COMP” or “DIS.
-
H/L” is selected by COMP MODE SEL.
Select the weight value for HI-HI limit, HI limit, LO limit, and LO
-
LO limit comparisons.
By selecting [COMP OFF], all comparisons are turned OFF.
Alternatives:
[
GROSS
]
[
NET
]
[
COMP OFF
]
■
Near zero comparison selection/ Preset near zero value
Valid in all comparison modes.
After selecting the weight value for comparisons, if the weight value
≦
preset near zero value, the
status display “NZ” lights, and the “NZ” output turns ON.
By selecting [COMP OFF], the “NZ” output is turned OFF.
NEAR ZERO COMP.:
[
GROSS
]
[
NET
]
[
COMP OFF
]
[
ABS GROSS
]
[
ABS NET
]
NEAR ZERO:
00000 to 99999
■
Tare setting selection/ Preset tare value
Valid in all comparison modes.
By turning [PRESET TARE WGT.1] ON, the net changes according to the following expression:
Net = Gross
-
Preset tare value
(However, if tare subtraction is input, the net weight becomes 0.)
PRESET TARE WGT.1:
[
OFF
]
[
ON
]
PRESET TARE WGT.2:
00000 to 99999
NEAR ZERO COMP.
Operation near zero
[GROSS]
ON when gross
≦
near zero setting
[NET]
ON when net
≦
near zero setting
[COMP OFF]
Always OFF
[ABS GROSS]
ON when | gross |
≦
near zero setting
[ABS NET]
ON when | net |
≦
near zero setting