10. SEQUENCE SETTING
Operation is performed by following the sequence that weighing is started by inputting the ON edge to
the start signal (external input/output connector pin B11) of the F600AT, and weighing is finished by
the completion signal.
This is valid only in the discharge mode.
Please refer to "11. TIMING CHART" on page 38 for each operation timing.
■
Control mode
Select sequence mode or simple comparison mode.
Alternatives:
[
SIMPLE COMP.
]
[
SEQUENCE
]
■
Adjust feeding/ Adjust feeding time
The setting is valid in the sequence mode.
ADJUST FEEDING:
[
OFF
]
[
ON
]
ADJ.FEEDING TIME:
0.00 to 9.99 (sec.)
What is “Adjust feeding”?
If the Net
<
Final weight – Under weight at the completion signal ON timing (when the judging time
has elapsed after the SP3 signal is turned OFF in the example on P.40), the completion signal is not
turned ON, but the SP3 signal is turned ON for the adjust feeding time.
Adjust feeding is valid only in the “Final discharge – Over weight/Under weight comparison mode”.)
■
Near zero confirmation at start time
The setting is valid in the sequence mode.
Alternatives:
[
OFF
]
[
ON
]
With the near zero confirmation at start time setting “ON,” When the start signal is
input, if the near zero signal is OFF, the feeding gate signal is not turned ON, but a
sequence error results. (Sequence error 4)