2: General Description
14
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18
2.5.3 UPS Control panel operator keys
Table 2.6 UPS Control panel operator keys
2.5.4
LCD Menu navigation
All the UPS control, monitoring and configuration functions are
actioned through a series of menus displayed on the LCD and
navigated using the control panel keys described in Table 2.6.
2.5.5 Main Menu
As shown in Figure 2.11, the main (top level) menu is accessed from
the Default screen by pressing the UP key for greater than 1 second. It
presents 6 options; Status, Event log, Measurements, Control,
Identification and Settings which can be scrolled through using the
UP/DOWN
keys.
Each Main Menu option has an associated sub-menu which can be
accessed by briefly pressing the
SELECT
key.
To return to the Default screen from any point in the menu tree, you
must press the
ON/OFF
key for less than one second.
Each of the Main Menu options is described below.
Operator
KEY
Function
Operation
Power ON / OFF
EXIT MENU
Press for 1s to turn ON the UPS.
Press for >3s to turn OFF the UPS or change the UPS operating mode between ‘on-
line’ and ‘on-bypass’.
Press for <1s to exit a menu and return to the default status screen.
SCROLL UP
From the default status screen, press for >1s to access the Main Menu.
Within a sub-menu press for <1s to scroll
UP
through the current menu options.
SCROLL DOWN
From default status screen, press for <1s to access the Status sub-menu.
Within a sub-menu press for <1s to scroll
DOWN
through the current menu options.
SELECT / EDIT
This key is used when editing the value of a parameter in the setup/configuration
menu screens. If pressed for less than one second it accepts the entered value and if
pressed for more than one second it saves the setting and exits the screen.
Key Point:
In the following description of the menu
navigation system the keys will be described as
ON/OFF
,
UP
,
DOWN
and
SELECT.
CAUTION: When pressing the ON/OFF button to exit a
menu take care not to hold the key pressed for longer than
3 seconds otherwise it will turn off the inverter and transfer
the load to bypass.
Mains
288V
v
v
v
HZ
HZ
W
v
100%
220
220
220
220
50
9000
50
Output
>1s
<1s
Measurements
Event Log
Status
Identification
Control
Settings
Figure 2.11 Menu navigation – Main Menu