TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18
57
8
Specifications
10kVA
10kVA
+5 min battery
10kVA
+16 min battery
20kVA
20kVA
+5 min battery
GENERAL
Output power factor
0.9
0.9
Rated output power (@ pf=0.8)
10 kVA
20 kVA
Rated output power (@ pf=1.0)
9 kW
18 kW
Weight
56 kg
117 kg
177 kg
66 kg
187 kg
Dimensions WxHxD
350x890x712
350x890x712
350x890x712
350x890x712
350x890x712
Colour
Pantone Process Black C
Topology
True on-line double conversion
INPUT CHARACTERISTICS
Nominal input voltage
1ph + N: 220 / 230 / 240 VAC 3ph + N: 380 / 400 / 415 VAC
Input voltage tolerance
1ph + N: 110-276 Vac 3ph + N: 190-486 Vac
Power factor
>0.99
Input power at rated output
(no batt charging)
9.68 kW
19.35 kW
1Ph Input current at rated output
(no batt charging)
44.4A / 42.5A / 40.7A
(@ 220V / 230V / 240V)
88.9A / 85.0A / 81.5A
(@ 220V / 230V / 240V)
3Ph Input current at rated output
(no batt charging)
14.9A / 14.1A / 13.6A
(@ 380V / 400V / 415V)
29.7A / 28.2A / 27.2A
(@ 380V / 400V / 415V)
Input power at rated output
(max batt charging)
10.99 kW
20.43 kW
1Ph Input current at rated output
(max batt charging)
50.5A / 48.3A / 46.2A
(@ 220V / 230V / 240V)
94.9A / 90.8A / 87.0A
(@ 220V / 230V / 240V)
3Ph Input current at rated output
(max batt charging)
16.9A / 16.0A / 15.4A
(@ 380V / 400V / 415V)
31.7A / 30.1A / 29.0A
(@ 380V / 400V / 415V)
Input current THD
<5% linear load, <7% non-linear load
Frequency range
45-55 Hz for 50 Hz system / 55-65 Hz for 60 Hz system
Frequency tolerance
±2%
NOTE: Technical specifications are subject to change without notice