General Description
2.1
Introduction
Congratulations on your purchase of the PowerWave PW3000/TP UPS.
Continuous power availability is essential in today’s dynamic IT and process-related work environments. It is equally
important that any installed power protection system is sufficiently resilient and adaptable to handle any changes brought
about by the introduction of new server technologies, migration and centralization.
Such demands are well met by the PowerWave PW3000/TP UPS system which provides the foundation for continuous
power availability of network-critical infrastructures both in enterprise data centres, where business continuity has
paramount importance, and in process control environments where manufacturing continuity is essential.
Reliability and quality standards
By using a unique modular construction and incorporating the latest technological developments in power engineering, the
PowerWave PW3000/TP represents a completely new generation of transformerless 3 phase UPS-System. Its advanced
double conversion VFI (Voltage and Frequency Independent) topology responds fully to both the highest availability and
environmentally friendly requirements compliant with IEC 62040-3 (VFI-SS-111) standards. A full UPS Specification is
contained in Chapter 8 of this manual.
Uninterruptible Power Supplies Ltd specialises in the installation and maintenance of Uninterruptible Power Systems; and
this powerful UPS is just one example of our wide range of state-of-the-art power protection devices that will provide your
critical equipment with a steady and reliable power supply for many years.
Key features
In addition to its high reliability, upgrade ability, low operating costs and excellent electrical performance the key features
of the PowerWave PW3000/TP include the following:
• Energy savings thanks to 93% AC-AC efficiency, 97% efficiency in ECO mode
• Low harmonic distortion (< 5% THDi) and active power factor correction (0.99 input PF) eliminates interference
from other network equipment
• Paralleling and redundancy capability – up to 4 units can be connected in parallel to increases the overall system
capacity and availability.
• Integrated automatic and manual bypass simplifies maintenance and reduces need for external switchgear.
• Frequency converter operation to convert 50 to/from 60 Hz
• Compact solution that can achieve 5-16min runtime with internal batteries
• Supports different wiring schemes: three-phase and single-phase input as well as single and dual input feed
• Matching external battery cabinet available for extended autonomy time