2: General Description
20
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18
Table 2.8 Settings sub-menu options
Sub-menu Item
Description
Values
Default
User password
Protects against unapproved access
Enabled / Disabled
Disabled
Language
Select menu language
English / Chinese
English
Audio alarm
Enable / disable alarm sounds
Enabled / Disabled
Enabled
Output voltage
Define local output voltage
200/208/220/230/240V
230V
Output frequency
Define local output frequency
(UPS detects the frequency in 'autosensing')
Autosensing /
50Hz / 60Hz
Autosensing
Power strategy
*
Define the operating mode
Normal / ECO- mode /
Frequency converter
Normal
DC start (Cold start)
Start the UPS from batteries, without mains power
Enabled / Disabled
Enabled
Automatic battery test period Define the frequency of the battery tests
0-31 days
7 days
Auto restart
After power outage, the load restart automatically
when mains power is recovered
Enabled / Disabled
Enabled
Automatic overload restart
The UPS automatically restarts if it shuts-down
due to overload
Enabled / Disabled
Enabled
Auto bypass
The automatic bypass can be disabled if the
bypass power supply is very unstable.
UPS runs only ‘on-line’ or on-battery.
Enabled / Disabled
Disabled
Short circuit clearance
When enabled, short circuit can last for 4s before
cutting off the output. If short circuit is removed
during this time, the UPS will continue to run.
When disabled, short circuit will only last
for 100ms before the UPS output is cut off.
Enabled / Disabled
Disabled
Bypass voltage low limit
When the voltage in the bypass is below this limit,
the UPS changes operating mode
176 ~ 215V
176V
Bypass voltage high limit
When the voltage in the bypass is above this limit,
the UPS changes operating mode.
245 ~ 276V
264V
Bypass frequency low limit
When the frequency in the bypass is above this
limit, the UPS changes operating mode.
40 ~ 49.5 Hz
45 Hz
Bypass frequency high limit
When the frequency in the bypass is above this
limit, the UPS changes operating mode.
50.5 ~ 70 Hz
55 Hz
HE voltage low limit
When the voltage in the bypass is below this limit,
the UPS changes operating mode.
1% ~1 0%
5%
HE voltage high limit
When the voltage in the bypass is above this limit,
the UPS changes operating mode.
1% ~ 10%
5%
HE frequency low limit
When the frequency in the bypass is below this
limit, the UPS changes operating mode.
1% ~ 10%
5%
HE frequency high limit
When the frequency in the bypass is above this
limit, the UPS changes operating mode.
1% ~ 10%
5%
External Battery modules
**
Define the number of external battery modules.
0 - 97
0
Set running time
Reset the UPS running time for tests purposes.
Day:hour:minute:second Running time
LCD contrast
Change the contrast in the LCD display
-5 ~ +5
0
Battery remaining time
When enabled, the battery remaining time is
displayed in the menu measurements
Enabled / Disabled
Disabled
* Read section 2.3 before using ECO-mode or converter function.
** Enter the number of ADDITIONAL (external) battery strings. An incorrect entry might degrade the battery operation.