3: Installation
24
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18
3.2.1 Site transportation
Please observe the following precautions when you transport the UPS equipment between its off loading site and the
intended installation (or storage) location.
3.3
Unpacking
Figure 3.1 Unpacking and positioning the PowerWave PW3000/TP
1. Using a forklift, move the unit to the location where it is to be installed.
Note:
The UPS has wheels to make final positioning easy after it has been unpacked, but these are not suitable for
moving the unit over long distances.
CAUTION: Potential dangers:
•
If the UPS/battery cabinet is tilted by more than 10° it could cause internal damage.
If tilting occurs, do not connect the UPS to the mains electrical supply.
•
The weight of the UPS/battery cabinet can cause serious personal injury and/or structural damage
to the surrounding area if dropped in transit. Always take extreme care when moving the equipment.
CAUTION: Storage:
•
The UPS should be stored in the original packing and shipping carton.
•
The recommended storing temperature for the UPS is b5°C and +40°C (+35°C for
batteries).
•
The UPS and the batteries must be protected from high humidity, which should not exceed 95% RH
(non-condensing).