EVO TM 

Uninterruptible Power Supply 

 
 

EVO TM 6.0 (6 KVA) 

EVO TM 8.0 (8 KVA) 

EVO TM 10.0 (10 KVA) 

EVO TM 12.0 (12 KVA) 

EVO TM 15.0 (15 KVA) 

 

 

 

 

USER’S MANUAL 

Summary of Contents for EVO TM 10.0

Page 1: ...EVO TM Uninterruptible Power Supply EVO TM 6 0 6 KVA EVO TM 8 0 8 KVA EVO TM 10 0 10 KVA EVO TM 12 0 12 KVA EVO TM 15 0 15 KVA USER S MANUAL...

Page 2: ......

Page 3: ...TALLATION 11 8 FIRST START UP 13 9 FUNCTIONING 14 10 COMPUTER INTERFACE 15 11 TECHNICAL CHARACTERISTICS 16 12 RECOMMENDATIONS FOR CORRECT USE 17 13 TROUBLESHOOTING 19 14 PICTURES 21 Copyright 2007 TEC...

Page 4: ...clines any responsibility if this warning is disregarded The electric installation has to be done by qualified personnel Follow all the Safety Standards CEI Standards in Italy for the IN OUT connectio...

Page 5: ...C AC converter Inverter UPS EVO TM protects the devices from accidental overload or Inverter fault by an AUTOMATIC BYPASS that directly connects the AC input line with its outlets The EVO TM models ar...

Page 6: ...matic shut down due to low battery once AC utility power comes back on Selectable input frequency 50 60 Hz Display LCD for visualization of the input and output voltage measurements batteries voltage...

Page 7: ...ce all around the UPS in order to keep it properly ventilated Do not obstruct ventilation holes Do not insert objects or pour liquids in the ventilation holes Do not rest any object on top of the UPS...

Page 8: ...after 90 seconds BYPASS MODE In BYPASS mode the AC input line is directly connected with the UPS outlets by an AUTOMATIC BYPASS As it is indicated in figure 1 in BYPASS mode the UPS recharge however...

Page 9: ...will supply the output power within 20 second OFF Button By pressing the OFF button for approximately 3 seconds the inverter is deactivated and the UPS switches in BYPASS mode SELECTION Button Using...

Page 10: ...w OVERLOAD Overload indication REAR SIDE To view the rear side of UPS EVO TM see figure 4 1 Main switch ON OFF is the general switch of the UPS in the OFF position it interrupts the input power line a...

Page 11: ...itch and then manually restart the UPS first moving again the main switch to the ON position end then press the front panel ON button The EPO terminals are isolated and do not need an external feeding...

Page 12: ...4 and Pin 1 10 will be closed Pin 5 is normal closed output when UPS works normally Pin 5 and Pin 1 10 will be closed when UPS works in AC failure mode Pin 5 and Pin 1 10 will be open 4 Bypass Pin 6...

Page 13: ...arting the installation procedure be sure that 1 Main ON OFF switch on the rear panel is OFF see figure 4 2 AC Input voltage for the UPS is OFF INSTALLATION Check the following operations 1 Remove the...

Page 14: ...uipment terminal GND of the UPS terminal blocks to the terminal GND on the BATTERY BOX 5 Reassemble the metallic panel that gives access to the terminal blocks 6 Place the switch of BATTERY BOX in the...

Page 15: ...al panel the led LINE and BYPASS still remains on and display LCD will light UPS EVO TM is functioning in BYPASS mode 6 After approximately 20 sec the inverter starts led LINE still remains on but the...

Page 16: ...INVERTER switches off and consequently there will be no output power WARNING As showed before in BYPASS mode the INVERTER is de activated and UPS EVO TM doesn t work as a UPS but only as a bypass bet...

Page 17: ...es overload condition Make sure that the UPS never indicates OVERLOAD Do not connect a load greater than rated value to the UPS see POWER specifications in the chapter TECHNICAL CHARACTERISTICS as thi...

Page 18: ...cc SEALED MAINTENANCE FREE LEAD ACID BATTERY 16 units 12V 7 2Ah 16 units 12V 9Ah 16 units 12V 9Ah 16 units 12V 9Ah 32 units 12V 9Ah SET POSITIONING BATTERIES Box battery RECHARGE TIME typical 8 ore AU...

Page 19: ...oved We recommend checking periodically the input power cord the output connections and the IN OUT Terminal Board LONG NOT WORKING PERIODS If EVO TM is not going to be used for a long period of time w...

Page 20: ...devices using the relative switches To turn off devices make following operations Turn off all devices using the relative switches Press OFF button on frontal panel so to generate switching in BYPASS...

Page 21: ...specified range disconnecting devices that generates overload UPS POWERED DEVICES DOESN T LIGHTS ON Before making following operations turn off the UPS positioning main switch on the rear side on OFF...

Page 22: ...re no internal parts in the UPS which are user serviceable Any repair or maintenance work must be performed exclusively by qualified technical personnel authorized by TECNOWARE TECNOWARE declines any...

Page 23: ...User s manual 21 UPS EVO TM 14 PICTURES Figure 1 Functioning mode...

Page 24: ...UNINTERRUPTIBLE POWER SUPPLY Figure 2A Frontal Panel for EVO TM 6 0 EVO TM 8 0 EVO TM 10 0 EVO TM 12 0 1 ON button 2 OFF button 3 SELECTION button 4 BATTERY LOW led yellow 5 OVERLOAD led red 6 FAULT l...

Page 25: ...User s manual 23 UPS EVO TM Figure 2B Frontal Panel for EVO TM 15 0 BUTTON LED LINE OFF Button UPS BYPASS ON Button FAULT BATTERY LOW SELECTION Button OVERLOAD...

Page 26: ...UPS EVO TM 24 User s manual Figure 3 IN OUT Terminal Blocks...

Page 27: ...s 1A AC input switch breaker 1B BATTERY switch breaker Main Switch in ON position means both switches 1A AC input breaker 1B and BATTERY breaker are in ON position Main Switch in OFF position means bo...

Page 28: ...any circumstances in which one cannot date back to the defective manufacture will not be covered by the guarantee Compensation is excluded for direct or in direct damages of any nature caused to peopl...