4: Operating procedures
46
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18
4.15 Emergency Stop
Details for the Emergency Power Off (EPO) circuit operation is given in Paragraph 7.2.
If the EPO circuit is activated it must be cleared through an LCD menu before the UPS can be returned to normal use.
To clear an EPO operation
1. From the default screen, press the
DOWN
key for one second to access
the Main Menu.
2. Scroll to the ‘Clear EPO Status’
screen, as shown [A].
3. Press the
SELECT
key.
a) The cursor will flash on
NO
.
4. If you want to clear the EPO status
use the
UP/DOWN
keys so that the
cursor indicates YES, then select it
by pressing the
SELECT
key for
less than one second [B].
5. The EPO status will now be
cleared.
6. Scroll back to the default LCD
display.
Measurements
Event Log
Control
Buzzer mute
Clear EPO Status
...............
Identification
Settings
..............
<1s
Figure 4.3 Clearing the EPO operation
A
B