2: General Description
18
TS_604_01 PowerWave PW3000/TP User Manual UK 5/1/18
Table 2.7 Control sub-menu options
2.5.10 Identification sub-menu
The Identification menu allows access to the UPS model
data, serial number and firmware revision details, as
shown in Figure 2.16. This information is often requested
when seeking assistance from the manufacturer or service
agent.
To access the Identification sub-menu you must highlight
the Identification option in the Main Menu then press the
SELECT
key for longer than one second. This opens the
Identification sub-menu screen which allows you to scroll
through the stored data using the
UP/DOWN
keys.
To exit the Identification sub-menu either press the
UP
key
for longer than one second to return to the Main Menu or
press the
ON/OFF
key for less than one second to return to
the default status screen.
2.5.11 Settings sub-menu
The Settings menu allows various UPS operating
parameters to be configured, as shown in Figure 2.17.
Some settings can impact on the UPS performance, others
can enable and disable functions within the UPS (see also
paragraph 2.3.4).
To access the Settings sub-menu you must highlight the Settings option in the Main Menu then press the
SELECT
key for
longer than one second. This opens the Settings sub-menu screen which allows you to scroll through the available options
using the
UP/DOWN
keys.
To exit the Settings sub-menu either press the
UP
key for longer than one second to return to the Main Menu or press the
ON/OFF
key for less than one second to return to the default status screen.
Control
Description
Values
Default
Buzzer Mute
Mute the audible warning alarm
No / Yes
No
*
Turn OFF Single UPS
Allows an individual module to be turned off.
No /Yes
No
UPS Battery Test
Initiate test of the batteries of a single UPS
Schedule / No / Yes
No
*
Parallel UPS battery test
Initiate test of the batteries of a group of UPS’s
Seg1 and Seg2: On /Off
On / Off
Clear EPO status
Reset the UPS from emergency power off status
No / Yes
No
Reset Fault state
Reset warning and alarming status and buzzer
No / Yes
No
Clear Event Log
Reset all the events from the log file
No / Yes
No
Restore factory setting
Restores default settings, EPO polarity and locks
the DC start-up
No / Yes
No
*Only relevant to multi-module installation
WARNING:
Inappropriately configured settings in this menu could result in reduced load protection or UPS
performance. This menu set-up or modified only by a qualified service engineer.
Type/Model:
UPS
PW3000/TP 10kVA
UPS firmware:
XXXX_XX
Serial Number:
XXXXXXXX
Measurements
Event Log
Status
Control
Identification
Settings
<1s
Figure 2.16 Menu Navigation – Identification