7: Options
7.5
AS400 Interface card
Figure 7.6 AS400 Pin assignment
The optional AS400 Interface card fits into the ‘AS400’ slot located on the back of the
PowerWave PW3000/TP. The card provides five UPS status/alarm outputs and monitors
three switched inputs via two 7-way Phoenix terminal blocks.
The card also contains an RS232 interface which can be used to configure the card’s
operation. Using some basic terminal communication software, such as Hyper terminal, it
is possible to change both the function and polarity of the relay; for example, to select an
individual switch segment to be Normally-Open or Normally-Closed, and immediate/
delayed operation. Detailed operating instructions are included in the option package.
RS232 Interface
The inbuilt RS232 interface is accessed via an RJ45 connector located adjacent to the I/O terminal blocks. An RJ45 to 9-
way D-Type adapter cable is provided with the equipment to allow connection to a computer’s serial port.
AS400 Alarm outputs
The switched outputs are configured as 5 segments:
The card’s internal volt-free contacts are rated at 250VAC/8A, 30VDC/8A,
110VDC/300mA, 220VDC/120A, and the terminal block accommodates
cables in the range 0.5 mm² to 1.5 mm².
WARNING:
The RJ45 connector must only be used for RS232 applications. If it is connected to a network
switch it may damage the UPS and/or network equipment.
Segment 1
Terminal 9-2
Utility (mains) Failure
Segment 2
Terminal 10-3
Battery Low
Segment 3
Terminal 11-4
General Alarm
Segment 4
Terminal 12-5
Bypass Status
Segment 5
Terminal 13-6
Summary Alarm