2: General Description
2.5.6 Status sub-menu
The Status sub-menu is slightly different from the other sub-
menus in that it can be accessed from two points: by
selecting the Status option in the Main Menu or directly from
the Default screen by briefly pressing the
DOWN
key. The
Status Sub-menu shows the following:
Alarm
Displays a list of any active alarms (an alarm history can be
obtained via the Event Log menu described below).
Normal indication is <No alarm>
Battery
The Battery menu displays:
• Battery Volt: <XXX V>
• Battery charge regime (e.g. <floating>)
• Charge level: XX%
Status and running time
This menu displays:
• Status: <Line Mode / Combo 3/1>
Indicates 3ph input and 1ph output and UPS is on-line
• Para Num: <X>
Indicates the number of parallel modules
• Running Time: <XXXX:XX:XX:XX>
Indicates the time for which the module has been
running (Days: Hrs: Mins: Secs)
2.5.7 Event Log sub-menu
The Event Log displays a date/time stamped list of the 50 most recent warning and fault events. Fault events are identified
by a corresponding event code. To access the Event Log you must highlight the Event Log option in the Main Menu then
press the
SELECT
key for longer than one second. This offers two further sub-menu options, from which you can choose
to view either Warnings or Faults. Once accessed, using the
SELECT
key, you can scroll through the log entries using the
UP/DOWN
keys. To exit the Event Log screen you must press the
ON/OFF
key for less than one second.
2.5.8 Measurements sub-menu
The Measurements menu allows various UPS operating
parameters to be observed, as shown in Figure 2.13.
To access the Measurements sub-menu you must highlight the
Measurement option in the Main Menu then press the
SELECT
key for longer than one second. This opens the Measurements
sub-menu screen which allows you to scroll through and
observe the monitored parameters using the
UP/DOWN
keys.
To exit the Measurements sub-menu either press the
UP
key
for longer than one second to return to the Main Menu or press
the
ON/OFF
key for less than one second to return to the
default screen.
Mains
288V
v
v
v
HZ
HZ
W
v
100%
220
220
220
220
50
9000
50
Output
Alarm
Battery
Status and
running time
>1s
Status Sub-menu
<1s
<1s
Measurements
Event Log
Status
Identification
Control
Settings
Figure 2.12 Menu navigation – Status Menu
Output power (W)
Output power (VA)
Output current (A)
Load percentage (%)
Output voltage (V)
Output frequency (Hz)
Input voltage (V)
Input frequency (Hz)
Bypass voltage (V)
Bypass frequency (Hz)
Battery voltage (V)
Battery capacity (%)
DC Bus voltage (V)
Temperature (deg. C)
<1s
Measurements
Event Log
Status
Control
Identification
Settings
Figure 2.13 Menu navigation – Measurements