2: General Description
Example: How to change the rated output voltage
Settings Menu (changing output voltage)
This example shows the steps necessary to change the UPS output voltage from its default 230V setting to 220V.
1. Gain access to the Main Menu and, using the
UP/DOWN
keys, scroll through to ‘Settings’ (A).
2. Press the
SELECT
key (<1s) to access the Settings sub-menu, starting at ‘Password’ or ‘Language’ (B).
Note that if the ‘User Password’ parameter has been set to <
disabled
> the ‘Password’ entry screen will be
bypassed and you will be taken straight to the ‘Language’ option.
3. Enter the password if required then press the
SELECT
key.
4. Using the
UP/DOWN
keys, scroll through the Settings sub-menu to ‘Output voltage,’ then press the
SELECT
key (<1s)
to access the ‘Output voltage’ change screen (C). Note that this may require password access if ‘set’.
5. The values shown in the change screen will initially flash.
6. Change the indicated value using the
UP/DOWN
keys to select the required voltage (220V) then press the
SELECT
key
for greater than one second to accept the change (D).
7. This will take you back to the Settings sub-menu where 220V will now be displayed in the Output voltage screen (E).
8. Continue scrolling through the Settings sub-menu using the
UP/DOWN
keys, and exit to the main Settings menu by
pressing the
UP
key for greater than one second; or exit back to the Default Screen by briefly pressing the
ON/OFF
key.
Language
<English>
Password:
<****>
User Password
<disabled>
Audio alarm
<enabled>
Output voltage
<230V>
Output frequency
<50Hz>
Output voltage
<
230
V
>
Output voltage
<
220
V>
Output voltage
<220V>
<1s
<1s
<1s
<1s
>1s
Settings
Measurements
Event Log
Status
Control
Identification
<1s
A
B
C
D
E
The Password entry screen will be
bypassed if the
USER
PASSWORD
setting
has be set to
<disabled>