3.
Remove Front Door Frame assembly by gently lifting the bottom edge of the
frame until it snaps off
(refer to Figure 1)
. Swing the bottom edge away until
the upper section is released.
4.
Mount 4-gang, 2-1/2" (6.4 cm) wall box with a 4-gang raised cover in wall at
desired location.
5.
Line Voltage Wiring:
NOTES:
• The insulation of the Class I field wiring must be rated no less than 75
°
C.
• Each screw terminal is capable of holding up to two (2) 12 AWG wires.
A.
Remove 3/8" (0.95 cm) of insulation from each circuit conductor. Make
sure that ends of conductors are straight.
B.
Connect conductors per WIRING DIAGRAM as follows
(refer to Figures
2 and 3)
: Insert conductors under appropriate terminal clamp and
tighten screws to 9 in.-lbs. of torque.
NOTE:
The Multizone Controller will automatically assign zone numbers
to loads based on which terminal you connect each load to. For
example: connecting a bank of fixtures to the Load 1 terminal means
that those fixtures will be the first Zone on that Multizone Controller. The
D3206 does allows you to change these zone numbers, if you desire.
6.
Low-Voltage Wiring (If LCnet wiring is required):
NOTES:
• If the device is the last one on the bus, the LCnet must be terminated. Use
the terminating plug (included) making sure to connect shorting wire to
CAN-L or you may also short the center terminal in the connector on the
device to the CAN-L terminal
(refer to Figure 3)
.
• LCnet must be wired using a twisted pair for the CAN_H and CAN_L
wires. Leviton recommends using CAT5 wire.
• DO NOT connect the 24VDC and GND power wires together in between
controllers when using multiple Multizone Controller applications.
• LCnet wires must also be dressed so they are separate from the high
voltage (Class I) conductors (use included tubing). Refer to local building
codes for the appropriate installation requirements for the low-voltage
wiring. Jacketing over the low-voltage wires may be required to provide
appropriate insulation from the high-voltage wiring.
Connect leads per WIRING DIAGRAM as follows
(refer to Figure 3)
: Insert
each lead into appropriate plug connector location by pushing firmly. If using
stranded wire, twist strands of each lead tightly (making sure that there are no
stray strands) and push firmly into appropriate plug connector location. Tighten
the screws on the plug connector—making sure that no bare conductor is
showing. Connect plug connector to jack on the back of the Controller.