7 Commands for parameter set up
47
<ch>: 0 ~ F(Hexadecimal) for channel.
Command HOLD?<ch>
Confirm the output of hold off signal.
Reply
OFF/ Enable the output of hold off signal.
ON/ Disable the output of hold off signal.
Example HOLD?3 reply: ON CH3’s hold off signal has disabled.
Remarks
Command H_ONTM<ch><t>
Set the time from excitation to the motor to actual movement.
Argument < t >
Excitation
time
Setting range: 50 to 3000 msec.
Initial value in 10ms increments 80msec.
Reply None
Example H_ONTM7500 Channel 7 operates 500ms after the holdoff is released.
Remarks Only remote mode.
Command H_ONTM?<Ch>
Check the time from exciting the motor to the actual movement.
Reply DDDmsec.
Example
H_ONTM? A Reply: 100 msec. Channel A will start operating 100ms after the holdoff is
released.
Remarks
Command
H_OFTM<ch><t>
HOLDTM<ch><t>
Set the time to output the hold-off signal after the motor has stopped.
Both commands have the same behavior.
Argument <t>
Excitation
time
Setting range: 50 to 3000 msec.
Initial value in 10ms increments 500 m sec.
Reply none
Example H_OFTMC1200 Channel C outputs a holdoff signal 1200ms after it has stopped.
Remarks Only remote mode.
Command
H_OFTM?<Ch>
HOLDTM?<Ch>
Check the time to output the hold-off signal after the motor has stopped.
Both commands have the same behavior.
Reply DDDmsec.
Example
H_OFTM? 5 Reply: 1000 msec. Channel 5 starts operation 1000ms after the holdoff is
released.
Remarks