Bit list for ReadCoil/WriteSingleCoil functions
Bit
Unit
Access
No.
Description
TCU3
TAM
TROX UNIVERSAL
Available with equipment function
FH
RR
RR
RMF
EC,
SC
TAM
TAM
RMF
RS/
RE
RS/RE
RMF
PR*/
PD*
PR*/PD*
RMF
0
ManOP_Disable
x¹
x
x
x
x
WR,
RD
1
PressSetSel
x
x
WR,
RD
2
Local Alarm
x
x
x
x
x
x
RD
3
SummaryAlarm
x
x
RD
4
PressAlarm
x
x
RD
5
SC_SetlockHigh-
Prio
Not used
6
SC_GetLockHigh-
Prio
Not used
7
SC_Alarm
Not used
8
LocalAlarm_0
x
x
x
x
x
x
RD
9
LocalAlarm_1
x
x
x
x
x
x
RD
10
LocalAlarm_2
x
x
x
x
x
x
RD
11
LocalAlarm_3
x
x
x
x
x
x
RD
12
LocalAlarm_4
x
x
x
x
x
x
RD
13
LocalAlarm_5
x
x
x
x
x
x
RD
14
LocalAlarm_6
x
x
x
x
x
x
RD
15
LocalAlarm_7
x
x
x
x
x
x
RD
16
LocalAlarm_8
x
x
x
x
x
x
RD
17
LocalAlarm_9
x
x
x
x
x
x
RD
18
LocalAlarm_10
x
x
x
x
x
x
RD
19
LocalAlarm_11
x
x
x
x
x
x
RD
20
LocalAlarm_12
x
x
x
x
x
x
RD
21
LocalAlarm_13
x
x
x
x
x
x
RD
22
LocalAlarm_14
x
x
x
x
x
x
RD
23
LocalAlarm_15
x
x
x
x
x
x
RD
24
LocalAlarm_16
x
x
x
x
x
x
RD
25
LocalAlarm_17
x
x
x
x
x
x
RD
26
LocalAlarm_18
x
x
x
x
x
x
RD
27
LocalAlarm_19
x
x
x
x
x
x
RD
1
only for individually selected operating mode (stand-alone operation)
Bits are read with function 1 (RD) or written with function 5 (WR).
Abbreviations
Interface information
Modbus interface
Expansion module EM-IP