VolflowSup
BMS access: WR RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, TAM, TAM with RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: l/s
Function
Integration of a supply air flow into the room balance
of the system
This default volume flow is considered for all volume
flow calculations (balance and setpoint values)
Data point
BACnet: Analog Value Object – Instance AV-23
Modbus: Register 42
SC_SetPos
Equipment function: not available
VolflowSet_R
BMS access: WR RD
Equipment function:
EASYLAB
–
not used
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: l/s
Function
Default setting of volume flow rate setpoint (room),
only for standard mode
Data point
BACnet: Analog Value Object – Instance AV-80
Modbus: Register 114
PressSet_R
BMS access: WR RD
Equipment function:
EASYLAB
–
not used
TROX UNIVERSAL
–
PR*/PD*, PR*/PD* with RMF
Unit: Pa
Function
Local default setting of room pressure or duct pres-
sure setpoint value
Data point
BACnet: Analog Value Object – Instance AV-81
Modbus: Register 115
Volt_AO2
BMS access: WR RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
not used
Unit: V DC
Function
Enabling/disabling manual control
Upon enabling manual control the corresponding
symbol appears on the control panel.
Default setting of voltage for analogue output AO2
0 – 10 V DC, in increments of 0.1 V
Data point
BACnet: Analog Value Object – Instance AV-84
Modbus: Register 118
Interface information
Data points – detailed description > Input variables
Expansion module EM-IP
49