DeviceObject
Property
Value
Access
Object identifier
Device instance; default = 17493
WR, RD; E
Device name
Default = "Device17493"; project-specific description can be
entered, 62 characters max.
WR, RD; E
Object type
Device (8)
RD
System_Status
OPERATIONAL (0)
RD
Vendor_Name
TROX GmbH
RD
Vendor_Identifier
329
RD
Model_Name
EM-IP
RD
Description
Default = “TROX EM-IP”; description can be entered,
126 characters max.
WR, RD; E
Location
Default = ""; description can be entered, 62 characters max. WR, RD; E
Firmware_Revision
V2.0
RD
Application_Software_Ver-
sion
TR2_02E
RD
Protocol_Version
1
RD
Protocol_Revision
12
RD
Protocol Services Sup-
ported
Who-is, Who-has, Read-Property, Write-Property, Device-
communication-control, Reinitialize-device
RD
Pro-
tocol_Object_Types_Sup-
ported
DEVICE, ANALOG_VALUE, BINARY_VALUE, MULTI-
STATE_VALUE
RD
Object_List
EASYLAB: device, analog-value 1…31, binary-value 1…30,
multistate-value 1…8
RD
Max_ADPU_Length_Accept
ed
1024
RD
Segmentation_Supported
NO_SEGMENTATION (3)
RD
APDU_Timeout
5000
RD
Number_Of_APDU_Retries 3
RD
Device_Address_Binding
–
RD
Database_Revision
0
RD
Access rights:
RD: Read
WR: Write
E: Save in EEPROM
Interface information
BACnet interface
Expansion module EM-IP
28