ManOp_Disable
BMS access: WR RD
Equipment function:
EASYLAB
–
FH, RR with RMF, TAM with RMF
TROX UNIVERSAL
–
RE/RS with RMF, PR*/PD* with RMF
Function
Enabling/disabling manual control
Upon enabling manual control the corresponding
symbol appears on the control panel.
For further information on manual control please
refer to the EASYLAB design manual.
FH: Operating mode default setting for a fume cup-
board controller, only with individual operating mode
default setting (stand-alone operation)
RMF: operating mode default setting for the entire
room
Functional values
0: Manual control has been enabled on the control
panel.
Operating mode defaults set on DI override BACnet
or Modbus defaults.
1: Manual control has been disabled on the control
panel.
Operating mode default settings from BACnet or
Modbus have the highest priority.
Data point
BACnet: Binary Value Object – Instance BV-4
Modbus: Bit list - bit 0 or register 1
PressSetSel
BMS access: WR RD
Equipment function:
EASYLAB
–
RR with RMF, TAM with RMF
TROX UNIVERSAL
–
not used
Function
Input for switching between two pressure set points
when differential pressure control of the system is
activated (setpoint values stored in the room man-
agement function).
Functional values
0: Use differential pressure setpoint 1
1: Use differential pressure setpoint 2
Data point
BACnet: Binary Value Object – Instance BV-5
Modbus: Bit list - bit 1 or register 13
DO*_Set (BACnet) / DO_Set (Modbus)
BMS access: WR RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Function
Control input signal for unused switch outputs DO1
– DO6 of the controller or adapter module
Data point
BACnet: Binary Value Object – Instance BV-19
(DO1_Set) – Instance BV-24 (DO6_Set)
–
0 = output inactive
–
1 = output active
Modbus: Register 61 – bit 0 (DO1_Set) – bit 5
(DO6_Set)
–
Bit not set = output inactive
–
Bit set = output active
Interface information
Data points – detailed description > Input variables
Expansion module EM-IP