DampPosMinState_FH
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
not used
Function
Output of the status of the fume cupboard controller
with the least wide open damper blade
5
For the evaluation of the damper blade positions in
separate extract air systems (2 fans), i.e. fume cup-
board extract air and room extract air
Data point
BACnet: Multistate Value Object – Instance MV-12
Modbus: Register 18
DampPosMaxState_RE
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
not used
Function
Output of the status of the room extract air controller
with the widest open damper blade
4
For the evaluation of the damper blade positions in
separate extract air systems (2 fans), i.e. fume cup-
board extract air and room extract air
Data point
BACnet: Multistate Value Object – Instance MV-13
Modbus: Register 20
DampPosMinState_RE
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
not used
Function
Output of the status of the room extract air controller
with the least wide open damper blade
5
For the evaluation of the damper blade positions in
separate extract air systems (2 fans), i.e. fume cup-
board extract air and room extract air
Data point
BACnet: Multistate Value Object – Instance MV-14
Modbus: Register 22
DampPosMaxState_TE
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
not used
Function
Output of the status of the fume cupboard, extract
air or room extract air controller with the widest open
damper blade
4
For the evaluation of the damper blade positions in
separate extract air systems (2 fans), i.e. fume cup-
board extract air and room extract air
Data point
BACnet: Multistate Value Object – Instance MV-15
Modbus: Register 24
Interface information
Data points – detailed description > Output variables
Expansion module EM-IP
59