DampPos
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position
1
Data point
BACnet: Analog Value Object – Instance AV-10
Modbus: Register 14
DampPosMax_FH
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
not used
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the fume
cupboard controller with the widest open damper
blade
1, 2, 4
For the evaluation of the damper blade positions in
separate extract air systems (2 fans), i.e. fume cup-
board extract air and room extract air
Data point
BACnet: Analog Value Object – Instance AV-11 –
value and event state
Modbus: Register 15 (value) and register 16 (event
state)
DampPosMin_FH
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
not used
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the fume
cupboard controller with the least wide open damper
blade
1, 2, 5
For the evaluation of the damper blade positions in
separate extract air systems (2 fans), i.e. fume cup-
board extract air and room extract air
Data point
BACnet: Analog Value Object – Instance AV-12 –
value and event state
Modbus: Register 17 (value) and register 18 (event
state)
DampPosMax_RE
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the room
extract air controller with the widest open damper
blade
1, 2, 4
For the evaluation of the damper blade positions in
separate extract air systems (2 fans), i.e. fume cup-
board extract air and room extract air
Data point
BACnet: Analog Value Object – Instance AV-13 –
value and event state
Modbus: Register 19 (value) and register 20 (event
state)
Interface information
Data points – detailed description > Output variables
Expansion module EM-IP
63