Volt_AI2
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
not used
Unit: V DC
Function
Output of the voltage at analogue input AI2
0 – 10 V DC, in increments of 0.1 V
Data point
BACnet: Analogue Value Object – Instance AV-82
Modbus: Register 116
Volt_AI3
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
not used
Unit: V DC
Function
Output of the voltage at analogue input AI3
0 – 10 V DC, in increments of 0.1 V
Data point
BACnet: Analogue Value Object – Instance AV-83
Modbus: Register 117
LocalAlarm
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Function
Output of a local alarm for a fume cupboard con-
troller, extract air controller, supply air controller,
room controller or TAM
Alarm conditions can be defined using the EasyCon-
nect configuration software.
Functional values
0 = No local alarm
1 = Local alarm
Data point
BACnet: Binary Value Object – Instance BV-1
Modbus: Bit list - bit 2 or register 31
Interface information
Data points – detailed description > Output variables
Expansion module EM-IP
56