DampPosMinValue_PKE
BMS access: RD
Equipment function:
EASYLAB
–
not used
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the extract
air pressure controller in the system with the widest
closed damper blade
1, 4
Data point
BACnet: Analog Value Object – Instance AV-90 –
value and event state
Modbus: Register 129 (value) and register 130
(event state)
DampPosMaxValue_PKS
BMS access: RD
Equipment function:
EASYLAB
–
not used
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the supply air
pressure controller in the system with the widest
open damper blade
1, 4
Data point
BACnet: Analog Value Object – Instance AV-91 –
value and event state
Modbus: Register 131 (value) and register 132
(event state)
DampPosMinValue_PKS
BMS access: RD
Equipment function:
EASYLAB
–
not used
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the extract
air pressure controller in the system with the widest
closed damper blade
1, 4
Data point
BACnet: Analog Value Object – Instance AV-92 –
value and event state
Modbus: Register 133 (value) and register 134
(event state)
Interface information
Data points – detailed description > Output variables